How to store lithium batteries safely, and how the European Battery Hub protects them in three stages: prevention, early detection, control.

In brief

Store lithium batteries safely in three stages.

To store lithium batteries safely, keep damaged batteries out of the warehouse, spot overheating early and make sure a fire stays confined to its area. The European Battery Hub (EBH) in Paderborn, Germany, does this in three stages: prevention through inspected goods receipt, detection through a fire alarm system, gas detection and a round-the-clock thermal imaging check by drone, and control through FM Global sprinklers, around 1 million liters of firefighting water and the containment box with BAM specification 15854.

For companies

How to store lithium batteries on your own premises

There is no single storage law for lithium-ion batteries. The requirements follow from the risk assessment, the German technical rule TRGS 510, the property insurer's requirements (above all the VdS 3103 information sheet) and the fire safety concept of the building. Clarify these points before your company stores batteries in-house.

  1. 01

    Classify

    Sort batteries under VdS 3103 into low, medium or high power. The protective measures depend on this.

  2. 02

    Distance or fire compartment

    Store batteries at a distance from other fire loads or in a separate fire compartment. The required distances are set by the insurer and the fire safety concept.

  3. 03

    Fire detection

    Automatic fire detection with an alarm connection, so that a fire is reported immediately outside working hours as well.

  4. 04

    Keep charging separate from storage

    Charging points should be physically separated from the storage area.

  5. 05

    Separate defective batteries

    Set damaged or abnormal batteries apart immediately, in suitable approved containers such as a battery containment box. More on damaged lithium batteries.

  6. 06

    State of charge and temperature

    Store batteries cool, dry and at the state of charge recommended by the manufacturer.

  7. 07

    Risk assessment and fire safety concept

    Document both in writing and agree them with your insurer and the fire department. The insurer's view is explained on the page about the insurable battery warehouse.

Decision guide

Store in-house or outsource?

Whether a company can store batteries in-house or should outsource depends mainly on quantity, power and condition.

Few batteries, low powerMany batteries, high power
  1. On your own premises

    Small quantities, low-power batteries

    Storage in a tested safety cabinet for lithium batteries or at a distance from fire loads on your own premises.

  2. Own fire compartment or external

    Larger quantities or medium and high-power batteries

    A separate fire compartment with fire detection and an agreed fire safety concept, or outsourcing to an external hazardous materials warehouse.

  3. External warehouse

    Large quantities and battery storage systems

    An external hazardous materials warehouse with fire suppression and thermal monitoring, such as the European Battery Hub.

Special case, regardless of quantity

Damaged or defective batteries

Set apart immediately in approved containers, transport under ADR special provision 376 (DDLB).

A rough guide. The risk assessment, the insurer and the fire safety concept are what count.

Understanding the risk

When a cell goes into thermal runaway

Lithium-ion cells can go into thermal runaway when they overheat, short-circuit or suffer mechanical damage: the cell keeps heating itself, and neighboring cells can fail one after another. Water cools and stops the spread, but it does not reliably end the reaction in the affected cell. The rule is therefore: cool and isolate the battery. Anyone who stores lithium batteries has to detect critical batteries early and contain them in space. The European Battery Hub does this with a temperature check at goods receipt, a round-the-clock thermal imaging check by drone, a fire alarm system and gas detection, FM Global sprinklers in the hazardous materials warehouse and the containment box for critical batteries. Other risks of lithium batteries, such as escaping electrolyte, and what to do in a battery fire are explained separately.

Safety from the ground up

Layer by layer, safe.

  1. 01Sealed hall floorwith fire water barrier
  2. 02Containment boxBAM specification 15854
  3. 03Zoned storageWGK 3, ADR Class 9 (M4)
  4. 04Thermal imaging droneThermal scans around the clock
  5. 05FM Global sprinklersaround 1 million liters of fire water
  6. 06Fire alarm system and gas detectionmonitor the warehouse
Safety in numbers

Documented protection values

01

FM Global suppression

Sprinkler system to FM Global, designed for hazardous materials; the fire water is retained inside the hall.

02

~1 million liters of water

The warehouse firefighting water tank holds around 1 million liters and supplies the sprinkler system.

03

WGK 3 Class 9 (M4)

A hazardous materials warehouse designed for substances of the highest water hazard class (WGK 3). The batteries are classified under ADR Class 9 with classification code M4 (UN3480 / UN3481).

FAQ

FAQ: how to store lithium batteries safely

How do you store lithium batteries safely?

Store lithium batteries at a distance from other fire loads or in a separate fire compartment, with automatic fire detection, in a cool, dry place and at the state of charge the manufacturer recommends. Set damaged batteries apart immediately in approved containers. The European Battery Hub adds a temperature check at goods receipt, a fire alarm system, gas detection, a round-the-clock thermal imaging check by drone, FM Global fire suppression and a hazardous materials warehouse designed for substances of water hazard class 3 (WGK 3).

Which regulations apply to storing lithium batteries?

There is no single law for storing lithium batteries. In Germany, the key requirements are the risk assessment under occupational safety and hazardous substances law, TRGS 510 for storing hazardous substances in mobile containers, the VdS 3103 information sheet of the property insurers, DGUV Information 205-041 “Brandschutz beim Umgang mit Lithium-Ionen-Batterien” (fire protection when handling lithium-ion batteries), and building law together with the building's fire safety concept. Transport is additionally governed by the ADR regulations.

Read more: TRGS 510 and storage classes, Insurable battery warehouse

From what quantity do I need a dedicated hazardous materials warehouse for batteries?

No single regulation sets a fixed quantity limit. Small quantities can often be stored in a tested safety cabinet for lithium batteries or at a distance from other fire loads. Whether that is enough is decided by the risk assessment, the fire safety concept and the property insurer, based on the quantity, power and condition of the batteries. For large quantities, high-power batteries or battery energy storage systems, a separate fire compartment or an external hazardous materials warehouse such as the European Battery Hub is the safe choice.

Read more: Hazardous materials warehouse for lithium batteries

How does the European Battery Hub detect an overheating battery early?

The European Battery Hub checks at two points. At the inbound inspection gate, batteries are checked for temperature and condition before they enter the warehouse; goods too large for the gate go through their own goods receipt processes. Inside the warehouse, a thermal imaging drone checks the stock around the clock with thermal imaging, and a fire alarm system and gas detection monitor the warehouse as well. The drone results feed, together with the inventory scan, into a digital twin of the warehouse.

Read more: Thermal imaging drone, Inbound inspection gate

How are lithium battery fires fought in the European Battery Hub warehouse?

In the European Battery Hub warehouse, an FM Global sprinkler system suppresses the fire. It is supplied by a firefighting water tank of around 1 million liters. Contaminated fire water stays inside the hall: the floors are sealed, and a fire water barrier is added. Water cools and stops the spread, but it does not reliably end the reaction in the affected cell. Critical batteries are therefore also isolated in the containment box.

Read more: Thermal runaway: causes, phases and extinguishing

What happens to critical or damaged batteries in an emergency?

At the European Battery Hub, critical batteries go into the containment box, a Liio-Box covered by BAM specification 15854. It withstands up to 1,240 °C inside while the outside stays at no more than 52 °C, and a stainless steel tray catches escaping electrolyte. We arrange removal through a specialized partner. In addition, the EBH is currently preparing a permanently installed emergency container outside the warehouse.

Read more: Battery containment box (Liio-Box), Shipping damaged lithium batteries

What do WGK 3 and ADR Class 9 (M4) mean for storing lithium batteries?

WGK 3 is the highest German water hazard class. The hazardous materials warehouse of the European Battery Hub is designed for substances of this class, so escaping substances are contained. ADR Class 9 with classification code M4 is the dangerous goods classification of lithium-ion batteries in transport: UN3480 for batteries shipped on their own, UN3481 for batteries contained in or packed with equipment.

Read more: Class 9 dangerous goods: UN3480 and UN3481

Outsource battery storage safely

Tell us the quantity, battery type and condition of your batteries. We review storage, transport and emergency response and get back to you within 24 hours on business days.