Contact
Energy stored. Future delivered.

Battery Storage Requirements

TRGS 510 governs how hazardous substances in non-stationary containers are stored and sets the lithium battery storage requirements.

At a glance

What does TRGS 510 require for lithium batteries?

TRGS 510 names lithium batteries in section 13.2 as an example of an increased short-circuit hazard. Under chemicals law, lithium-ion batteries are articles. Formally, they are therefore not hazardous substances under the GefStoffV, and TRGS 510 does not apply to them directly. Good practice is to store them in line with TRGS 510 on the basis of a risk assessment. This is also how the European Battery Hub (EBH) in Paderborn, Germany, stores them.

TRGS 510 "Storage of hazardous substances in non-stationary containers" (December 2020 edition, GMBl. 2021 p. 178) puts the German Hazardous Substances Ordinance (GefStoffV) into practice. A company that complies with it can assume it meets the corresponding requirements of the ordinance. The 24 storage classes (LGK) serve only to control co-storage; dedicated stores, quantity thresholds and fire protection are covered by other sections of the TRGS.

Anyone who stores lithium-ion batteries applies these lithium battery storage requirements by analogy and draws up a risk assessment. The reason is the fire hazard: a short circuit or damage can trigger thermal runaway, which can spread to neighboring cells.

Which storage class do lithium batteries have?

The names follow the flow chart for assigning storage classes in annex 2 of TRGS 510; LGK 9 is not used. As articles, lithium batteries have no CLP classification, and the class 9 hazard label is not one of the criteria in the flow chart. Manufacturers therefore often assign lithium-ion batteries to storage class 11; the safety data sheet is decisive, and the storage class is set in the risk assessment.

LGKName
LGK 1Explosive hazardous substances
LGK 2AGases
LGK 2BAerosol dispensers and lighters
LGK 3Flammable liquids (including desensitised explosive liquids)
LGK 4.1AOther explosive hazardous substances
LGK 4.1BFlammable solid hazardous substances (including desensitised explosive solids)
LGK 4.2Pyrophoric or self-heating hazardous substances
LGK 4.3Hazardous substances that emit flammable gases in contact with water
LGK 5.1AStrongly oxidizing hazardous substances
LGK 5.1BOxidising hazardous substances
LGK 5.1CAmmonium nitrate and preparations containing ammonium nitrate
LGK 5.2Organic peroxides and self-reactive hazardous substances
LGK 6.1ACombustible, highly acutely toxic hazardous substances
LGK 6.1BNon-combustible, highly acutely toxic hazardous substances
LGK 6.1CCombustible, acutely toxic or chronically harmful hazardous substances
LGK 6.1DNon-combustible, acutely toxic or chronically harmful hazardous substances
LGK 6.2Infectious substances
LGK 7Radioactive substances
LGK 8ACombustible corrosive hazardous substances
LGK 8BNon-combustible corrosive hazardous substances
LGK 10Combustible liquids not assigned to LGK 1 to 8
LGK 11Combustible solids not assigned to LGK 1 to 8
LGK 12Non-combustible liquids
LGK 13Non-combustible solids

Which rules apply to stores, fire protection and distances?

Quantity thresholds and the dedicated store

TRGS 510 defines quantity thresholds for each hazard class. Once these are exceeded, hazardous substances may only be kept in a dedicated store, a structurally separated area used exclusively for storage. Below the thresholds, storage in workrooms is possible subject to conditions. With lithium batteries, the high energy content alone often leads to stricter requirements.

Fire protection and fire compartments

The central protective measures are fire compartments, suitable suppression technology, fire detection and a well thought-out storage concept. For lithium batteries, temperature monitoring, early detection of thermal anomalies and an emergency response plan are decisive as well, because a thermal runaway is very hard to extinguish. Many property insurers also require measures in line with VdS 3103 (insurable battery storage).

Co-storage and separation distances

Section 13 of TRGS 510, with its co-storage table (table 12), governs whether goods may be stored together, apart or entirely separately. The principle: goods may only be stored together if this does not increase the hazard; section 13.2 explicitly names the ignition hazard from short circuits in lithium batteries. Separate storage means sufficient distances or barriers, such as walls, cabinets made of non-combustible material or products made of non-combustible substances of LGK 12 or 13. Segregated storage means different storage sections with a fire resistance of at least 90 minutes. The rules of section 13 apply where storage in a dedicated store under section 5 is required, and not for a total quantity of all hazardous substances of up to 200 kg. Defective or damaged batteries are always kept apart from intact stock.

Operator duties

What is required: a risk assessment, operating instructions, regular staff training, suitable protective measures and documentation of them. Stores above certain quantities are subject to additional organizational and, where applicable, building-law requirements.

At a glance

Storage, fire protection and distances on the plan

Choose a rule. The plan shows where it applies in the warehouse.

Lithium batteriesOther stored goodsBarrierFire wall, min. 90 minutesLGK 3 and 5.1ChargingDefective goodsDetectors and sprinklers

Co-storage

The principle: goods may only be stored together if this does not increase the hazard; section 13.2 explicitly names the ignition hazard from short circuits in lithium batteries.

Separate storage

Separate storage means sufficient distances or barriers, such as walls, cabinets made of non-combustible material or products made of non-combustible substances of LGK 12 or 13.

Segregated storage

Segregated storage means separate storage sections with a fire resistance of at least 90 minutes.

Keep apart

In practice, oxidizing substances (LGK 5.1A to 5.1C) and flammable liquids (LGK 3) are kept away from lithium batteries.

Separate charging and storage

Keep charging and storage physically apart.

Remove defective goods

Remove defective batteries immediately and store them separately. The EBH does not store damaged batteries; they go into the containment box.

Fire detection and suppression

The central protective measures are fire compartments, suitable suppression technology, fire detection and a well thought-out storage concept. Fire detection should report a fire early, and the suppression technology should be matched to lithium batteries.

Schematic storage plan, not the EBH floor plan. The risk assessment is what counts.

Checklist

How should lithium batteries be stored? A checklist in 10 points

  1. 01: Draw up and document a risk assessment. This checklist does not replace it.
  2. 02: A dedicated storage section or a suitable safety cabinet.
  3. 03: Keep a distance or structural separation from other stored goods.
  4. 04: Provide fire detection that reports a fire early.
  5. 05: Match the suppression technology to lithium batteries.
  6. 06: Keep charging and storage physically apart.
  7. 07: Remove defective batteries immediately and store them separately.
  8. 08: Draw up and display operating instructions.
  9. 09: Train staff regularly and keep records.
  10. 10: Involve your insurer early; many require measures in line with VdS 3103.
Aisle in the EBH hazardous materials warehouse: red high-bay racking with battery crates on pallets, a forklift in the background

How does the EBH store lithium batteries?

The European Battery Hub stores lithium-ion batteries in Paderborn in a hazardous materials warehouse built in 2023/24, with 20,300 m² of storage space and 45,000 storage spaces. It is designed for Class 9 lithium batteries (classification code M4) and for water-polluting substances up to WGK 3. Structural fire protection consists of an FM Global sprinkler system, a firefighting water tank holding around 1 million liters that supplies the sprinkler system, and sealed hall floors with a fire water barrier.

At the inbound inspection gate, batteries are temperature-checked; goods too large for the gate go through their own goods receipt processes. In the warehouse, the thermal imaging drone checks the stock around the clock, and a fire alarm system and gas detection monitor the warehouse as well. The EBH does not store damaged batteries; if a battery shows anomalies, it goes into the battery containment box. Find out more about our hazardous materials warehouse for batteries and our insurable battery warehouse; what takes effect in a fire is covered under how to store lithium batteries.

Contacts

Your contacts

Talk directly with our business development team.
We will get back to you within 24 hours on business days.

FAQ

Common questions about TRGS 510 and storage classes

Does TRGS 510 apply to lithium batteries?

Not formally, but in practice it is followed. Under chemicals law, lithium batteries are articles and not classified hazardous substances, but TRGS 510 names them in section 13.2 as an example of an increased short-circuit hazard. Formally, TRGS 510 therefore does not apply to them; good practice is storage in line with TRGS 510 on the basis of the risk assessment, often supplemented by property insurer requirements under VdS 3103.

Which storage class do lithium-ion batteries have?

Usually storage class 11: manufacturers often assign lithium-ion batteries to this class, and the safety data sheet is decisive. As articles, batteries have no GHS classification, so the storage class is set in the risk assessment. The storage class only controls co-storage. In practice, oxidizing substances (LGK 5.1A to 5.1C) and flammable liquids (LGK 3) are kept away from lithium batteries.

How must lithium-ion batteries be stored under TRGS 510?

The starting point is a risk assessment. It usually leads to a dedicated storage section or safety cabinet, distance or structural separation from other goods, fire detection that reports early, suppression technology suited to lithium batteries and separate handling of defective stock. Charging and storage are kept physically apart. The checklist in this guide sums up the ten most important points.

At what quantity do lithium batteries need a dedicated store?

TRGS 510 sets no fixed quantity limit for lithium batteries, because its thresholds are tied to the classification of hazardous substances. What counts is the risk assessment and often the property insurer's requirements under VdS 3103. Because of the high stored energy, even comparatively small quantities often lead to structural and fire protection requirements.

How are defective lithium batteries stored?

Defective or damaged batteries are separated from intact stock immediately, because their risk of thermal runaway is much higher. TRGS 510 distinguishes separate storage (distances or barriers) from segregated storage (dedicated storage sections with at least 90 minutes of fire resistance). The EBH does not store damaged batteries; they can only be kept in the battery containment box with BAM specification 15854, which withstands up to 1,240 °C inside.

Read more: Damaged lithium batteries

Do lithium batteries need firefighting water retention?

As a rule yes, at least for larger quantities. As articles, batteries have no fixed water hazard class, but electrolyte and fire residues are considered water-polluting, and lithium battery fires are often fought with large volumes of water. The EBH warehouse is designed for water-polluting substances up to WGK 3 and retains contaminated firefighting water inside the hall, with sealed floors and a fire water barrier.

Which regulations apply to the storage of hazardous substances in Germany?

The basis is the German Hazardous Substances Ordinance (GefStoffV). TRGS 510 puts it into practice for storage in non-stationary containers such as packagings, IBCs and containers; complying with it means the ordinance can be assumed to be met. For lithium batteries, the risk assessment, often the property insurer's requirements under VdS 3103 and, depending on the store, building regulations come on top.

Store batteries in line with TRGS 510?

We store your lithium-ion batteries in our hazardous materials warehouse in Paderborn, with a temperature check on arrival, a fire alarm system, gas detection and a round-the-clock thermal imaging check. Our team gets back to you within 24 hours on business days.

Response
within 24 hours on business days