TRGS 510 governs how hazardous substances in non-stationary containers are stored and sets the lithium battery storage requirements.
TRGS 510 names lithium batteries in section 13.2 as an example of an increased short-circuit hazard. Under chemicals law, lithium-ion batteries are articles. Formally, they are therefore not hazardous substances under the GefStoffV, and TRGS 510 does not apply to them directly. Good practice is to store them in line with TRGS 510 on the basis of a risk assessment. This is also how the European Battery Hub (EBH) in Paderborn, Germany, stores them.
TRGS 510 "Storage of hazardous substances in non-stationary containers" (December 2020 edition, GMBl. 2021 p. 178) puts the German Hazardous Substances Ordinance (GefStoffV) into practice. A company that complies with it can assume it meets the corresponding requirements of the ordinance. The 24 storage classes (LGK) serve only to control co-storage; dedicated stores, quantity thresholds and fire protection are covered by other sections of the TRGS.
Anyone who stores lithium-ion batteries applies these lithium battery storage requirements by analogy and draws up a risk assessment. The reason is the fire hazard: a short circuit or damage can trigger thermal runaway, which can spread to neighboring cells.
The names follow the flow chart for assigning storage classes in annex 2 of TRGS 510; LGK 9 is not used. As articles, lithium batteries have no CLP classification, and the class 9 hazard label is not one of the criteria in the flow chart. Manufacturers therefore often assign lithium-ion batteries to storage class 11; the safety data sheet is decisive, and the storage class is set in the risk assessment.
| LGK | Name |
|---|---|
| LGK 1 | Explosive hazardous substances |
| LGK 2A | Gases |
| LGK 2B | Aerosol dispensers and lighters |
| LGK 3 | Flammable liquids (including desensitised explosive liquids) |
| LGK 4.1A | Other explosive hazardous substances |
| LGK 4.1B | Flammable solid hazardous substances (including desensitised explosive solids) |
| LGK 4.2 | Pyrophoric or self-heating hazardous substances |
| LGK 4.3 | Hazardous substances that emit flammable gases in contact with water |
| LGK 5.1A | Strongly oxidizing hazardous substances |
| LGK 5.1B | Oxidising hazardous substances |
| LGK 5.1C | Ammonium nitrate and preparations containing ammonium nitrate |
| LGK 5.2 | Organic peroxides and self-reactive hazardous substances |
| LGK 6.1A | Combustible, highly acutely toxic hazardous substances |
| LGK 6.1B | Non-combustible, highly acutely toxic hazardous substances |
| LGK 6.1C | Combustible, acutely toxic or chronically harmful hazardous substances |
| LGK 6.1D | Non-combustible, acutely toxic or chronically harmful hazardous substances |
| LGK 6.2 | Infectious substances |
| LGK 7 | Radioactive substances |
| LGK 8A | Combustible corrosive hazardous substances |
| LGK 8B | Non-combustible corrosive hazardous substances |
| LGK 10 | Combustible liquids not assigned to LGK 1 to 8 |
| LGK 11 | Combustible solids not assigned to LGK 1 to 8 |
| LGK 12 | Non-combustible liquids |
| LGK 13 | Non-combustible solids |
TRGS 510 defines quantity thresholds for each hazard class. Once these are exceeded, hazardous substances may only be kept in a dedicated store, a structurally separated area used exclusively for storage. Below the thresholds, storage in workrooms is possible subject to conditions. With lithium batteries, the high energy content alone often leads to stricter requirements.
The central protective measures are fire compartments, suitable suppression technology, fire detection and a well thought-out storage concept. For lithium batteries, temperature monitoring, early detection of thermal anomalies and an emergency response plan are decisive as well, because a thermal runaway is very hard to extinguish. Many property insurers also require measures in line with VdS 3103 (insurable battery storage).
Section 13 of TRGS 510, with its co-storage table (table 12), governs whether goods may be stored together, apart or entirely separately. The principle: goods may only be stored together if this does not increase the hazard; section 13.2 explicitly names the ignition hazard from short circuits in lithium batteries. Separate storage means sufficient distances or barriers, such as walls, cabinets made of non-combustible material or products made of non-combustible substances of LGK 12 or 13. Segregated storage means different storage sections with a fire resistance of at least 90 minutes. The rules of section 13 apply where storage in a dedicated store under section 5 is required, and not for a total quantity of all hazardous substances of up to 200 kg. Defective or damaged batteries are always kept apart from intact stock.
What is required: a risk assessment, operating instructions, regular staff training, suitable protective measures and documentation of them. Stores above certain quantities are subject to additional organizational and, where applicable, building-law requirements.
Choose a rule. The plan shows where it applies in the warehouse.
The principle: goods may only be stored together if this does not increase the hazard; section 13.2 explicitly names the ignition hazard from short circuits in lithium batteries.
Separate storage means sufficient distances or barriers, such as walls, cabinets made of non-combustible material or products made of non-combustible substances of LGK 12 or 13.
Segregated storage means separate storage sections with a fire resistance of at least 90 minutes.
In practice, oxidizing substances (LGK 5.1A to 5.1C) and flammable liquids (LGK 3) are kept away from lithium batteries.
Keep charging and storage physically apart.
Remove defective batteries immediately and store them separately. The EBH does not store damaged batteries; they go into the containment box.
The central protective measures are fire compartments, suitable suppression technology, fire detection and a well thought-out storage concept. Fire detection should report a fire early, and the suppression technology should be matched to lithium batteries.
Schematic storage plan, not the EBH floor plan. The risk assessment is what counts.

The European Battery Hub stores lithium-ion batteries in Paderborn in a hazardous materials warehouse built in 2023/24, with 20,300 m² of storage space and 45,000 storage spaces. It is designed for Class 9 lithium batteries (classification code M4) and for water-polluting substances up to WGK 3. Structural fire protection consists of an FM Global sprinkler system, a firefighting water tank holding around 1 million liters that supplies the sprinkler system, and sealed hall floors with a fire water barrier.
At the inbound inspection gate, batteries are temperature-checked; goods too large for the gate go through their own goods receipt processes. In the warehouse, the thermal imaging drone checks the stock around the clock, and a fire alarm system and gas detection monitor the warehouse as well. The EBH does not store damaged batteries; if a battery shows anomalies, it goes into the battery containment box. Find out more about our hazardous materials warehouse for batteries and our insurable battery warehouse; what takes effect in a fire is covered under how to store lithium batteries.
Storage of lithium-ion batteries on 20,300 m² in Paderborn, with a temperature check on arrival.
See the hazardous materials warehouseWhat property insurers expect when lithium batteries are stored and what the EBH has in place for this.
See the insurable battery warehouseWhat happens when a battery stands out in the warehouse: from the first warning sign to quarantine in the battery containment box.
See the emergency response planTalk directly with our business development team.
We will get back to you within 24 hours on business days.

Head of Business Development

Business Development Manager

Business Development Manager
Not formally, but in practice it is followed. Under chemicals law, lithium batteries are articles and not classified hazardous substances, but TRGS 510 names them in section 13.2 as an example of an increased short-circuit hazard. Formally, TRGS 510 therefore does not apply to them; good practice is storage in line with TRGS 510 on the basis of the risk assessment, often supplemented by property insurer requirements under VdS 3103.
Usually storage class 11: manufacturers often assign lithium-ion batteries to this class, and the safety data sheet is decisive. As articles, batteries have no GHS classification, so the storage class is set in the risk assessment. The storage class only controls co-storage. In practice, oxidizing substances (LGK 5.1A to 5.1C) and flammable liquids (LGK 3) are kept away from lithium batteries.
The starting point is a risk assessment. It usually leads to a dedicated storage section or safety cabinet, distance or structural separation from other goods, fire detection that reports early, suppression technology suited to lithium batteries and separate handling of defective stock. Charging and storage are kept physically apart. The checklist in this guide sums up the ten most important points.
TRGS 510 sets no fixed quantity limit for lithium batteries, because its thresholds are tied to the classification of hazardous substances. What counts is the risk assessment and often the property insurer's requirements under VdS 3103. Because of the high stored energy, even comparatively small quantities often lead to structural and fire protection requirements.
Defective or damaged batteries are separated from intact stock immediately, because their risk of thermal runaway is much higher. TRGS 510 distinguishes separate storage (distances or barriers) from segregated storage (dedicated storage sections with at least 90 minutes of fire resistance). The EBH does not store damaged batteries; they can only be kept in the battery containment box with BAM specification 15854, which withstands up to 1,240 °C inside.
Read more: Damaged lithium batteries
As a rule yes, at least for larger quantities. As articles, batteries have no fixed water hazard class, but electrolyte and fire residues are considered water-polluting, and lithium battery fires are often fought with large volumes of water. The EBH warehouse is designed for water-polluting substances up to WGK 3 and retains contaminated firefighting water inside the hall, with sealed floors and a fire water barrier.
The basis is the German Hazardous Substances Ordinance (GefStoffV). TRGS 510 puts it into practice for storage in non-stationary containers such as packagings, IBCs and containers; complying with it means the ordinance can be assumed to be met. For lithium batteries, the risk assessment, often the property insurer's requirements under VdS 3103 and, depending on the store, building regulations come on top.
We store your lithium-ion batteries in our hazardous materials warehouse in Paderborn, with a temperature check on arrival, a fire alarm system, gas detection and a round-the-clock thermal imaging check. Our team gets back to you within 24 hours on business days.